Gasmet Industrial Computer

Gasmet industrial computer is required to operate the analyzer, to control the sampling system, translate measured and analyzed concentrations and alarms to higher level automation and control systems.

In essence, the Gasmet software (Calcmet) can be operated by any Windows computer. However, many typical continuous monitoring applications require analog inputs and outputs, relay contacts, status input and output values, all of which can optionally be provided by adding desired expansion cards to the Gasmet industrial computer.

The standard computer configuration provides analyzer control via a serial port, watchdog support and remote control for service and troubleshooting purposes. Additional features including sampling system control, current and alarm outputs and multipoint sampling can be realized by adding suitable expansion cards to the computer.

SYSTEMS TO OPERATE WITH

  1. Gasmet Continuous Emissions monitoring system (CEMS II)
  2. Gasmet Engine Emissions Monitoring system (EEMS)
  3. Gasmet In-situ
  4. Gasmet Multipoint Sampling systems (MSS & MSSH)
  5. Gasmet CR1000, CR2000 or CR4000
  6. Gasmet CX4000 or CX4015

Technical Data

Standard configuration
Normal configuration: Intel® Core™ i3-330E 2.13 GHz processor, 1 GB DDR3-SDRAM memory, 2 x 3.5” SATA HDD, RAID 1, Back-up hard disk (empty) and docking station, DVD-RW drive, USB modem, network card (2 pcs), pcAnywhere (host)
Operating system: Windows 7 (32-bit) (English)
Software included: Calcmet STD for Windows
Watchdog support: Included
Mouse: Optional
Keyboard: Optional

 

Optional input / output expansion cards
AdLink PCI cards:  
- Analogue output 8 x 4-20 mA / card
- Digital input / output 16 x input / 16 x output / card
- Relay output 8 / card
- Analogue input 8 x 0-10 V / card (max. 8 cards)

 

 Optional input / output expansion modules
Built in weather proof casing or on DIN rail.
Enclosure:  IP66
Beckhoff:  
- Digital output 8 x 0.5 A / module
- Digital input 8 / module
- Analogue output 8 x 4-20 mA / module
- Analogue input 4 x 4-20 mA / module,
4 x 0-10 V / module
(max. 255 modules)
FieldBus: ModBus, ModBus TCP/IP, Profibus, ASCII, DDE link. RS232 or RS422/485

 

Remote control
Remote control: Built-in modem/network card and pcAnywhere support

 

Electrical connections
Mouse: PS/2
Keyboard: PS/2
Display: DVI-I


 

EMI protection / electrical safety
CE label: According to EMI guideline 89/336/EC


 

Enclosure
Dimensions: 19" rack, height 4 U
431 x 487 x 176 mm (WxDxH)
Weight: 16.7 kg

Gasmet Technologies Oy shall not be liable for technical or editorial errors or omissions contained herein. The information in this document is provided “as is” without warranty of any kind and is subject to change without notice. Should you find any errors, we would appreciate if you notified us.